By Wu Peng, Senior Process Instrumentation Engineer · Last reviewed October 14, 2026
A displacer level transmitter measures level by weighing a long cylinder, the displacer, that hangs in the liquid. As the level rises, the liquid pushes up on the displacer with a force equal to the weight of liquid it displaces, so its apparent weight falls. A torque tube or a range spring turns that weight change into a small rotation or movement, and the electronics convert it to 4-20 mA. The displacer itself moves only slightly.
Displacers are still common in high-pressure liquid service, such as the natural gas production, compression and processing applications Fisher’s bulletin names, often in an external cage. They are simple and rugged, but every reading depends on the specific gravity the instrument was set up for. This guide works through the force math, calibration numbers, interface service and density error. It also answers the cut-to-length question that comes up on old level controllers.
Contents
- How it works
- Torque tube or spring
- Sizing the displacer
- Dry calibration weights
- Wet calibration
- Interface measurement
- Density and temperature
- Cutting a displacer
- Retrofit options
- Troubleshooting
- FAQ
How it works
The physics is Archimedes. A displacer of weight W and volume V, submerged to a fraction f of its length in a liquid of specific gravity SG, has a net downward force of:
Apparent weight = W − f × V × SG × ρw × g
With the level below the displacer, f = 0 and the instrument sees the full weight. With the displacer fully covered, f = 1 and the apparent weight is at its minimum. Between those two points the change is linear with level, so the length of the displacer sets the measuring range. It reads force, not the surface, so foam and vapor above the liquid affect it far less than a sensor aimed at the surface.
Caged displacer. The cage shares the vessel level through two side nozzles; the torque tube seals the process and carries the force change to the transmitter.
Torque tube or spring
Two mechanisms carry the force out of the pressure boundary. In a torque tube design, the displacer hangs from an arm welded to a thin-walled tube. The tube is the pressure seal and also a torsion spring, so the force change twists it by a few degrees. Fisher specifies a nominal 4.4 degrees of torque tube rotation for a 0 to 100% level change in water, and WIKA’s DTT manual describes about 4 degrees.
In a spring design, the displacer hangs from a range spring. An LVDT (linear variable differential transformer) reads its small vertical movement through an enclosing tube, as in Magnetrol’s E3 Modulevel. The spring sets the force-per-millimeter, and the enclosing tube acts as the isolation barrier between the LVDT and the process. Both designs work on the same force balance, so the sizing and calibration math below applies to either.
Sizing the displacer
Choose the length from the range, then check that the volume gives enough force change at your SG. The force change over the full span is V × SG × ρw × g. Light liquids give a smaller change from the same displacer, which is why vendors publish a minimum SG or a minimum SG difference for each displacer size.
| Source | Published figures |
|---|---|
| Fisher 249 / DLC3010 bulletin | Standard volumes 1016 cm³ (62 in³) for 249C/CP, 1622 or 1360 cm³ for most others; minimum differential SG 0.05 |
| Masoneilan 12400 | Standard displacer 1362 g, 907 cm³; SG 0.15 to 1.4; ranges 356 to 3048 mm |
| WIKA DTT | Range 300 to 3000 mm; medium SG 0.1 to 1.5; minimum interface SG difference 0.1 |
| Kimray (level controllers) | Standard displacer senses an interface if the SG difference is larger than 0.2 |
Figures from each vendor’s bulletin or manual. They apply to that vendor’s displacers and torque tubes only.
Fisher’s bulletin explains where those limits come from, using proportional band: the share of the nominal torque tube rotation that the measured span actually uses. The electronics can stretch a small rotation to full output, down to 5% of the nominal span. The cost is accuracy: “operating at 5% proportional band will degrade accuracy by a factor of 20.” Fisher adds that a thin-wall torque tube or a doubled displacer volume each roughly doubles the band, and suggests one of them once it drops below 50%.
Dry calibration weights
A dry or bench calibration hangs weights on the torque arm in place of the displacer, one weight for each test point. Masoneilan’s 12400 manual gives the rule: apparent weight = actual displacer weight − (displacer volume × calibration SG). Its own example for water is 1362 − 907 × 1 = 455 g.
Here is the full five-point table for the same standard displacer (1362 g, 907 cm³) in a hydrocarbon with SG 0.80. Each point is 1362 − 907 × 0.80 × f:
| Level | Fraction f | Test weight | Output |
|---|---|---|---|
| 0% | 0 | 1362.0 g | 4 mA |
| 25% | 0.25 | 1180.6 g | 8 mA |
| 50% | 0.50 | 999.2 g | 12 mA |
| 75% | 0.75 | 817.8 g | 16 mA |
| 100% | 1.00 | 636.4 g | 20 mA |
These figures use the displacer alone. If a hanger or stem also hangs on the arm in service, add its weight to every point, and use the actual weight and volume from the tag or manual when they differ from nominal.
Note the direction: the weight goes down as the level goes up, so each step removes weight. Step lists that say “add weight” for a rising level have it backwards. If the loop runs from 20 mA to 4 mA as you remove weight, the action is set to reverse.
Wet calibration
Wet calibration fills the cage with water instead of process liquid, which is easier on site. Stop at the water height that produces the same force as 100% process level. The water-equivalent height is the process SG times the range.
Take an 813 mm (32 in) displacer in a liquid with SG 0.80. Set 100% at 0.80 × 813 = 650.4 mm (25.6 in) of water above the displacer bottom, and 0% with the cage drained below the displacer. Water at full range would push the output past 20 mA and saturate the loop. Drain, flush and dry the cage before returning a hydrocarbon or water-sensitive service.
Interface measurement
For an interface between two liquids, the displacer must stay fully submerged at all times. Masoneilan and Magnetrol both state this in their documentation. The output then moves from the force at “all light liquid” to the force at “all heavy liquid”, so the span depends on the SG difference, not on either SG alone.
With the same 907 cm³ displacer, a light liquid of SG 0.85 over water gives 1362 − 907 × 0.85 = 591.05 g at 0% and 455.0 g at 100%. The full span is only 136.05 g, which is 15% of the 907 g change the same displacer gives in water. On a Fisher standard displacer, the same 0.15 SG difference gives about a 15% proportional band. That is well under the 50% at which Fisher suggests a larger displacer or a thin-wall torque tube.
Density and temperature
A displacer measures force, so a change in SG looks exactly like a change in level. For level service the indicated level is the true level times SGactual / SGcalibration. A unit calibrated at SG 0.80 that sees a lighter batch at SG 0.76 reads 95% when the true level is 100%. That is an error of 5% of reading, with nothing wrong in the instrument.
Checking the SG of each new batch catches the shift early. A portable density meter takes that reading at the tank or on a sample, with a repeatability of ±0.001 g/cc.
Temperature changes the reading in two ways. Liquid density falls as it warms, and the torque tube gets softer. Emerson’s calibration supplement notes that “as process temperature increases, the torque rate decreases,” so enable temperature compensation on hot service. Torque tube materials also have limits: Fisher states that N05500 (nickel-copper alloy) torque tubes are not recommended for spring applications above 232 °C (450 °F), and Masoneilan requires an Inconel torque tube above 260 °C (500 °F).
On high-pressure gas service, the vapor above the liquid also has weight. The buoyancy change from 0 to 100% then depends on SGliquid − SGvapor, so a light hydrocarbon near its critical point has a smaller span than its liquid SG suggests. Enter both densities where the electronics allow it.
Cutting a displacer
People ask whether a displacer on a level controller can be cut to length to fit a shorter vessel or change the range. We found no manufacturer document that allows it. The Fisher 249 manual calls the displacer “a sealed container” and warns that one holding pressure or liquid can release it if “punctured, subjected to heat, or repaired.” Cutting one open does exactly that.
Even an unused displacer no longer matches its calibration once shortened. Volume, weight and length all drop, so every calibration point moves, and Masoneilan’s manual says recalibration is required whenever the displacer’s actual characteristics differ from the standard values. Order the correct length from the manufacturer, or recalibrate the existing one for the range it can cover.
Kimray takes the same route in its training note: where its 2 in x 20 in displacer is too long for a smaller vessel, it recommends a 3 in x 12 in displacer on a flanged or large plate adapter instead.
Retrofit options
Some displacers keep drifting with density or sticking with deposits. Other level technologies can take over. These are the options in our range and how they compare on density, deposits and cage maintenance:
| Option | Fit as a displacer replacement |
|---|---|
| Guided wave radar | Measures travel time, so the level reading does not depend on density. The 705 model covers −200 to 400 °C and up to 40 MPa; the 704 coaxial probe suits low-dielectric liquids. |
| Magnetic level gauge | External chamber with a float matched to the liquid density, up to 20 MPa and 450 °C by type. A clamp-on 4-20 mA/HART transmitter adds a continuous signal outside the seal. |
| DP level transmitter | Uses the same two vessel nozzles; still density dependent, like a displacer. Spans from 4 kPa. |
| Magnetostrictive | ±0.1 mm or 0.05% FS; standard to +125 °C, +200 °C with extension. |
Values from our product datasheets. We do not list a torque-tube displacer transmitter; check the cage dimensions and connections before choosing a retrofit.
Radar has its own limits: interface work needs enough difference in dielectric constant, as covered in dielectric constant and radar level. For a wider view, see the comparison of level transmitter types and our level instruments range. If the liquid is dirty and the tank is open, a bubbler level measurement keeps every part but a dip tube out of the process.

Application note
Typical displacer retrofit request. A displacer retrofit review starts with the existing cage on the vessel. The useful data are the cage center-to-center distance and connection style, the pressure class, the liquid SG range, any interface, and the operating temperature. With those, the choice between radar in the existing cage, a magnetic gauge with a transmitter, or DP becomes a short comparison.
Troubleshooting
Most displacer faults show up as a level that is off by a steady amount or stuck in one place.
| Symptom | Likely cause and check |
|---|---|
| Reads low by a steady % | Actual SG lower than the configured SG. Compare a lab sample with the setting. |
| Reads low, worsening slowly | Deposits adding weight to the displacer. Pull and clean it, then compare its weight with the tag value. |
| Stuck or jumps in steps | Displacer or stem touching the cage wall. Check cage plumb and stem straightness. |
| Stuck near 0% with liquid present | Displacer full of liquid. Handle it as pressurized per the manufacturer’s warning; do not puncture or heat it. |
| Zero shifts with temperature | Torque rate change; enable temperature compensation or calibrate at operating temperature. |
| Saturates after water calibration | Water filled to the full range instead of SG × range. Recalculate the water-equivalent height. |
Isolate the cage before any bench work, and treat a displacer from hydrocarbon service as a pressure container until it is proven empty. For a related check on still pipes and float wells, see our stilling well guide.
FAQ
What is a displacer level transmitter?
It is a level instrument that hangs a long cylinder in the liquid and measures its apparent weight. Buoyancy rises with level, a torque tube or spring converts the force change to movement, and the electronics output 4-20 mA, usually with HART.
What is the working principle of a displacement level transmitter?
Archimedes’ principle. The upward force on the displacer equals the weight of the liquid it displaces, so the apparent weight is W minus the submerged volume times the liquid density and g. That force change is linear with level over the displacer length.
How do you calibrate a level transmitter?
For a displacer, either hang test weights equal to the apparent weight at 0% and 100% (dry), or fill the cage with water to SG times the range for 100% (wet). Then check midpoints at 25%, 50% and 75% and confirm the configured SG matches the process.
Request a quote
Send the cage connection style and center-to-center distance, pressure class, operating temperature, liquid SG range and any interface. Tell us the application and we configure one unit, not a shelf part. Reach our application engineers or use the form below.
Written and technically reviewed by Wu Peng and the Instranova engineering team.